CONTROLSTIK,Rinse,Tank,System,Myron L Company

CONTROLSTIK Rinse Tank System From Myron L Company

The Myron L CONTROLSTIK Rinse Tank System dramatically reduces the amount of water used in continuous flow rinse tanks.  At the same time, it automatically maintains optimum water purity, ensuring effective rinsing.

How it works 
The three parts of the CONTROLSTIK System are easily installed.  The CONTROLSTIK (conductivity sensor) is set at a tolerable contamination level and submerged in the tank.  Water cannot flow into the tank until drag-in from rinsed parts causes the contamination level in the tank to rise above the pre-set point.  The CONTROLSTIK (sensor) then signals the solenoid valve to open, adding fresh water.  As soon as this fresh water dilutes the contamination to the tolerable pre-set level, the CONTROLSTIK (sensor) closes the valve.

Since water flows only when parts are rinsed, you save money on water bills, sewer use charges, and waste water treatment expenses.

CONTROLSTIK Rinse Tank System

Features

Cuts water consumption up to 85%

CONTROLSTIK,Rinse,Tank,System,Myron L Company

Reliable solid-state electronics
Corrosion-resistant design
Minimal maintenance
Panel or surface mount design
Attractive panel design allows for
either surface or panel mounting

Model 595 Dual Range CONTROLSTIK Rinse Tank System
Standard, simple, inexpensive automatic monitor/control for rinse water.

CONTROLSTIK,Rinse,Tank,System,Myron L Company

CONTROLSTIK,Rinse,Tank,System,Myron L Company
Model 597 Dual Range CONTROLSTIK II Rinse Tank System
 
A Heavy-Duty corrosion-resistant automatic monitor/control for rinse water.

Transformer Box Specifications

Input Power
Choice of 120 or 240 VAC, 50/60 Hz, Automatic voltage regulation ensures operation of the systems from 105-125VAC or 210-250VAC respectively
Output
24 VAC @ 600 milliamps AC
Maximum power consumption
12 watts (103 milliamps) @ 117 VAC
Lights
LEDs indicate POWER (red) and VALVE (yellow)
Line cord
8' (2.4m), 18 ga., 3 conductor plug (with 115VAC system only)
Installation
Mounts easily in panel; or on wall (surface mounting plate provided)
Terminal strip for fast wiring
Enclosure
Model 595 Controlstik only - ABS corrosion resistant plastic
Model 597 Controlstik II only - NEMA 12 fiberglass case with heavy gasket and 316 stainless steel hardware
597 Electrical Installation
Either HARDWIRE with 5/8" conduit, or PLUG-IN with 8' (2.4m), 18 ga., 3-conductor plug (supplied with 120VAC systems only)

CONTROLSTIK Sensor Specifications

Ranges
5-500 micromhos (for high quality water);
500-5000 micromhos (for normal tap water)
Power
1 VAC (from transformer box)
On-Off Span
Approximately 5% of setpoint
Temperature Compensation
Automatic to 180°F (82°C)
Cord
10' (3m) 22 ga., 4 conductor, vinyl jacketed (longer cords available)
Installation
ABS bracket supplied
Materials
Epoxy and 316 stainless steel
Dimensions
12" (304mm) Long, 1" (25mm) Diameter

Solenoid Valve Specifications

Size
1" NPT normally closed - compatible with plastic or metal piping
Power
24 VAC (from transformer box)
Materials
Body - glass reinforced nylon;
Diaphragm - nylon reinforced BUNA N synthetic rubber;
All exposed metal - stainless steel
Operating Pressure
10-100 psi (69-690 kPa)
Miscellaneous
Adjustable flow control; manual override; anti-hammer closing, conduit connector